ManBetX网页版登录(万博)卓越股份有限公司|官网

Consultation Hotline: 400-101-3651

110kV Oil-Immersed Transformer


110kV three-phase oil-immersed power transformer is manufactured in conformity with IEC60076 standards (applicable International Electrotechnical Commission standards) and GB1094 standards (applicable state standards of the People's Republic of China). This series of transformers features excellent impact resistance, high mechanical strength, strong short circuit resistance, low partial discharge, low noise, nice sealing performance and less maintenance. It is widely used as the main transformer in power stations, transformer substations and power transmission and transformation systems of urban and rural power grids.

Product introduction



Working Conditions:
No.
Conditions
Units
Parameter Values
1
Pollution Grade
 
IV
2
Ambient Temperature
Maximum Daily Temperature
40
Minimum Daily Temperature
-45
Maximum Daily Temperature Difference
K
25
Average Temperature of the Hottest Month
30
Maximum Annual Average Temperature
20
3
Humidity
Average Daily Relative Humidity
%
≤95
Average Monthly Relative Humidity
≤90
4
Altitude
m
1000
5
Solar Radiation Intensity
W/cm2
0.1
6
Maximum Icing Thickness
mm
10
7
Maximum average wind speed: keeping in good conditions for 10min at 10m from the ground level
m/s
35
8
Earthquake Resistance
Horizontal Ground Acceleration
m/s2
2
Safety Coefficient of 3 Since Resonance Cycles
 
≥1.67
9
Installation Site
 
Outdoor
Note 1: Working conditions in high altitude regions (above 1000m) must be adjusted in conformity with Q/GDW 13001-2014 (High Altitude External Insulation Configuration Technical Specification).
 

Product Parameters:
Table 1  110kV - 6300kV.A ~ 180000kV.A, Three-Phase Duplex Windings, No-Load Voltage Regulation, Power Transformer
Rated Capacity
(kV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
High Voltage & Tapping Range (kV)
Low Voltage (kV)
6 300
110±2×2.5%
115±2×2.5%
121±2×2.5%
6.6
6.6
10.5
YNd11
7.40
35.0
0.62
10.5
8 000
8.90
42.0
0.62
10 000
10.5
50.0
0.58
12 500
12.4
59.0
0.58
16 000
15.0
73.0
0.54
20 000
17.6
88.0
0.54
25 000
20.8
104
0.50
31 500
24.6
123
0.48
40 000
29.4
148
0.45
50 000
35.2
175
0.42
63 000
41.6
208
0.38
75 000
13.8
15.75
18
21
47.2
236
0.33
12~14
90 000
54.4
272
0.30
120 000
67.8
337
0.27
150 000
80.1
399
0.24
180 000
90.0
457
0.20
Note 1: -5% is the maximum current tapping position.
Note 2: Boosting transformers are suitable for no-tap structure. Taps can also be arranged to meet operating requirements.
Note 3: If transformers’ annual average load rate is between 42% and 46%, using loss values in this Table can obtain the highest operating efficiency. 


Table 2 110kV - 6300kV.A ~ 63000kV.A, Three-Phase Triplex Windings, No-Load Voltage Regulation, Power Transformer
Rated Capacity
(kV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
High Voltage & Tapping Range (kV)
Medium Voltage (kV)
Low Voltage (kV)
Boost
Buck
6 300
110±2×2.5%
115±2×2.5%
121士2×2.5%
36
37
38.5
6.3
6.6
10.5
11
YNyn0d11
8.9
44.0
0.66
High-Medium
17.5~18.5
High-Low
10.5
Medium-Low
6.5
 
High-Medium
10.5
High-Low
18~19
Medium-Low
6.5
 
8 000
10.6
53.0
0.62
10 000
12.6
62.0
0.59
12 500
14.7
74.0
0.56
16 000
17.9
90.0
0.53
20 000
21.1
106
0.62
25 000
24.6
126
0.48
31 500
29.4
149
0.48
40 000
34.8
179
0.44
50 000
41.6
213
0.44
63 000
49.2
256
0.40
Note 1: Capacity assignment of high voltage winding, medium voltage winding and low voltage winding is (100/100/100)%.
Note 2: Connection symbol can also be YNdlly10 upon demands.
Note 3: “Medium Voltage” can use different values from this Table or arrange taps upon demands.
Note 4: -5% is the maximum current tapping position.
Note 5: Boosting transformers are suitable for no-tap structure. Taps can also be arranged to meet operating requirements.
Note 6: If transformers’ annual average load rate is about 45%, using loss values in this Table can obtain the highest operating efficiency. 


Table 3 110kV - 6 300kV.A ~ 63 000kV.A, Three-Phase Duplex Windings, On-Load Voltage Regulation, Power Transformer
Rated Capacity
(kV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
High Voltage (kV)
Low Voltage (kV)
6 300
110±8×1.25%
6.3
6.6
10.5
21
YNd11
8.00
35.0
0.64
10.5
8 000
9.60
42.0
0.64
10 000
11.3
50.0
0.59
12 500
13.4
59.0
0.59
16 000
16.1
73.0
0.55
20 000
19.2
88.0
0.55
25 000
22.7
104
0.51
31 500
27.0
123
0.51
40 000
32.3
156
0.46
12~18
50 000
38.2
194
0.46
63 000
45.4
232
0.42
Note 1: On-load voltage regulation transformers only have Buck structure products.
Note 2: Transformers of other voltage combinations can be supplied upon demands.
Note 3: -10% is the maximum current tapping position.
Note 4: If transformers’ annual average load rate is between 45% and 50%, using loss values in this Table can obtain the highest operating efficiency. 


Table 4 110kV - 6 300kV.A ~ 63 000kV.A, Three-Phase Triplex Windings, On-Load Voltage Regulation, Power Transformer
Rated Capacity
(kV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
High Voltage & Tapping Range (kV)
Medium Voltage (kV)
Low Voltage (kV)
6 300
110±8×1.25%
36
37
38.5
6.3
6.6
10.5
21
YNyn0d11
9.60
44.0
0.76
High-Medium
10.5
High-Low
17.5~18.5
Medium-Low
6.5
 
8 000
11.5
53.0
0.76
10 000
13.6
62.0
0.71
12 500
16.1
74.0
0.71
16 000
19.3
90.0
0.67
20 000
22.8
106
0.67
25 000
27.0
126
0.62
31 500
32.1
149
0.62
40 000
38.5
179
0.58
50 000
45.5
213
0.58
63 000
54.1
256
0.58
Note 1: On-load voltage regulation transformers only have Buck structure products.
Note 2: Capacity assignment of high voltage winding, medium voltage winding and low voltage winding is (100/100/100)%.
Note 3: Connection symbol can also be YNdlly10 upon demands.
Note 4: -10% is the maximum current tapping position.
Note 5: “Medium Voltage” can use different values from this Table or arrange taps upon demands.
Note 6: If transformers’ annual average load rate is about 47%, using loss values in this Table can obtain the highest operating efficiency. 


Table 5 110kV - 6300kV.A ~ 63000 kV.A, Three-Phase Duplex Windings, Low Voltage 35kV, No-Load Voltage Regulation, Power Transformer
Rated Capacity
(kV.A)
Voltage Combination & Tapping Range
Connection Symbol
No-Load Loss (kW)
On-Load Loss (kW)
No-Load Current (%)
Short-Circuit Impedance (%)
High Voltage & Tapping Range (kV)
Low Voltage (kV)
6 300
110±2×2.5
115±2×2.5
121±2×2.5
36
37
38.5
YNd11
8.00
37.0
0.67
10.5
 
8 000
9.60
44.0
0.67
10 000
11.2
52.0
0.62
12 500
13.1
62.0
0.62
16 000
15.6
76.0
0.57
20 000
18.5
94.0
0.57
25 000
21.9
110
0.53
31 500
25.9
133
0.53
40 000
30.8
155
0.49
50 000
36.9
193
0.49
63 000
43.6
232
0.45
Note 1: -5% is the maximum current tapping position.
Note 2: Boosting transformers are suitable for no-tap structure. Taps can also be arranged to meet operating requirements.
Note 3: If transformers’ annual average load rate is between 44% and 47%, using loss values in this Table can obtain the highest operating efficiency. 

Address: No.1, West Xuefu Road, Longling Industrial Park, Gaoxin District, Yiyang City, Hunan Province, 413000, China

Contact No.: 0737-2222100

QQ: 3013508896

E-mail: huaxiangbyq@163.com

©2018 All Rights Reserved by Huaxiang Xiangneng Technology Co., Ltd.     湘ICP备11006305号-2